Data Sheet for the
Liebert NX 30 UPS

 

Best Price

Liebert NX 30 UPS

NX-30
Liebert NX 30kVa / 24 kW UPS, 120/208V
Liebert-NX-30

A high-efficiency 3-phase UPS. Suitable for large business application.

Output | Input | Battery | Communications & Management | Conformance
| Dimensions and Weight | Options

Output
top

Output Voltage, VAC: 380/400/415
Supply:
3 phase, 4-wire plus ground
Rated Power, kW:
24
Frequency, Hz:
50 / 60
Three-phase transient overload, min. load: 10 minutes-105 to 125% load, 1 minute 125 to 150% load
Voltage Regulation:
+/- 1% three-phase RMS average for a balanced three phase load; +/- 2% three-phase RMS average for a 100% unbalanced load
Maximum rate of change of Frequency, Hz/sec:
For single mode, slew rate is adjustable from 0.1Hz/s to 3Hz/s
Current rating of neutral cable, A:
1.5 X input current

Topology: Double Conversion
Waveform Type:
Sine wave

Nominal Output Current: 84
OCP Current: 105
OCP Device Rating:
110
Bolt Size:
6M (1/4")
Max Recommended Lug T&B One Hole 54000:
54108
Max Recommended Lug T&B One Hole REDDY:
62205


Input
top

Input Voltage Range: 304-477V
Input Voltage:
380/400/415 VAC 3-ph, 4-w
Input Frequency:
50 or 60 Hz
Input Frequency Range:
40-72 Hz
Input THDI at nominal Voltage:
<3% without additional hardware

Nominal Input Current: 83
Maximum Input Current:
104
OCP Current:
125
OCP Device Rating:
125
Bolt Size:
6M (1/4")
Max Recommended Lug T&B One Hole 54000:
54152
Max Recommended Lug T&B One Hole REDDY:
62205


Rectifier Input (dual input units only)

Nominal Input Current: 75
Maximum Input Current:
94
OCP Current:
113
OCP Device Rating:
125
Bolt Size:
6M (1/4")
Max Recommended Lug T&B One Hole 54000:
54152
Max Recommended Lug T&B One Hole REDDY:
62205


Bypass Input

Rated Voltage, VAC: 120/208
Supply:
3 phase, 4-wire plus ground
Rated Current, A 208VAC:
83
Frequency, Hz:
50 / 60
Input Frequency Tolerance %:
+/- 10% or +/- 20%; default +/- 20%
Bypass Voltage Tolerance %:
Upper Limit +20% default 15%, Lower limit -40%, default -20%
Current rating of neutral cable, A:
1.5 X input current
Bypass Overload capacity:
+Long term operation: <135% of load; 10 minutes: 135%-170% full load; 100milliseconds: 1000% full UPS rated output current


Bypass Input (dual input units only)

Nominal Input Current: 83
OCP Current: 104
OCP Device Rating:
110
Bolt Size:
6M (1/4")
Max Recommended Lug T&B One Hole 54000:
54152
Max Recommended Lug T&B One Hole REDDY:
62205

 


Battery
top

Compatibility to VRLA (SMF), LATB, Nickel Cadmium batteries

Customer Replaceable Parts available :

Battery Brand: Either Enersys Yuasa (NPX-80FR, NPX-100FR or NPX-150FR) or C&D Dynasty (UPS12-100MR or UPS12-140MR)
Battery Type:
VRLA
Quantity (Batteries or Cells or Jars): 24 Jars, 144 Cells
Nominal Float Voltage:
288 VDC (2 volts per cell)
Recommended Float Charge Voltage:
2.27 VDC
Recommended Boost Charge Voltage:
2.3 VDC
Recommended End of Discharge Voltage:
1.68-1.8 VDC
Maximum Recharge Battery Current, A:
15
Maximum Boost Charge Duration, mins:
1440
Boost-float Threshold Current, A:
0.1 C default
Temperature Voltage Compensation, mV/ °C:
3
Ripple Voltage Superimposed %:
less than or equal to 1

Battery Current: 110
OCP Current: 110
OCP Device Rating:
125
Bolt Size:
8M (5/16")
Max Recommended Lug T&B One Hole 54000:
54153
Max Recommended Lug T&B One Hole REDDY:
62212

 

 

Communications & Management
top

User Interface: LCD display in twelve different languages
Three (3) intellislots to house multiple cards including:
• Relay Card (to address the basic need of users / maintenance persons)
• SNMP Web Card (to address the needs of network managers)
• ModBus / Jbus Card

Communication Ports: RS-232 and RS-485


Conformance
top

Agency Approvals: IEEC 1000-4-5; ASME; CSA 22.2, No. 107.1; FCC Part 15, Class A; ISO 9001; NFPA-70; NEMA PE-1; OSHA; UL 1778, UL and c-UL
Standard Warranty: 1 year



Dimensions and Weights
top

NX-30:

Physical

Maximum Height: 1600 mm / 63 ins
Maximum Width:
600 mm / 24 ins
Maximum Depth:
825 mm / 32.5 ins
Net Weight- without batteries: 250 KG / 550 lbs
Net Weight- UPS 12-100:
478 KG / 1054 lbs
Net Weight- UPS 12-140: 543 KG / 1198 lbs

Environmental

Operating Environment: 0 - 40 °C
Optimal Operating Temperature- Battery: 0 - 40 °
Relative Humidity: 0 - 95%, non-condensing
Acoustical noise at 1 meter from surface of unit: 54.00 dBA°
Operating Elevation: < or = 1000 meters per IEC 62040/3
Storage Transport Temperature-UPS: -20 to 70 °C
Storage Transport Temperature-Battery: -20 to 30 °C
Storage Elevation: 0-12200 meters

Mechanical Characteristics

Airflow, CFM: 834 CFM
Online Thermal Dissipation: 8300 BTU/hr
Cooling:
Fan Cooled
Cable Entry: Top or Bottom
Color: PMS 877 (Cream)
Protection Grace (w. open/closed front doors):
IP 20

 

Options
top

Maintenance ByPass Cabinet

Battery Circuit Breaker Box

Narrow Battery Cabinet

Wide Battery Cabinet

 




Where to Buy: Liebert NX-30,Liebert NBATTMOD, Liebert Npower-50 , Liebert Npower-65, Liebert Npower-BC

IBM Parts : HP Parts : Sun Parts : Dell Parts : SAN - Fiber Channel HBA's




Legal Disclaimer:  this site is in no way endorsed or affiliated with APC, Oracle or Sun Microsystems, Inc. This site is independently run and in no way represents APC, Oracle or Sun Microsystems, Inc. Oracle or Sun Does not officially sponsor, approve, or endorse this site or its content. THIS DOCUMENTATION IS PROVIDED "AS IS" AND ALL EXPRESS OR IMPLIED CONDITIONS, REPRESENTATIONS AND WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR NON-INFRINGEMENT ARE DISCLAIMED, EXCEPT TO THE EXTENT THAT SUCH DISCLAIMERS ARE HELD TO BE LEGALLY INVALID. Content on this web site is provided for informational purposes only. We accept no responsibility for any loss, injury or inconvenience sustained by any person resulting from information published on this site.